Technical dataEL6733
Technology PROFIBUS master/slave terminal
Cycle time differing DP cycle times per slave are possible using the CDL concept
Fieldbus PROFIBUS DP (standard)
Number of fieldbus channels 1
Data transfer rates 9.6 kbaud…12 Mbaud
Interfaces 1 x D-sub socket, 9-pin, galvanically decoupled
Bus device max. 125 slaves with up to 244 bytes input, output, parameter, configuration or diagnostic data per slave
Hardware diagnostics status LEDs
Distributed clocks yes
Bit width in the process image total max.: 1.4 kbyte input and 1.4 kbyte output data
Current consumption power contacts –
Weight approx. 70 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable