Technical dataBK7520
Number of Bus Terminals 64 (255 with K-bus extension)
Max. number of bytes fieldbus 254 word I/O for the cyclic interface (depending on the master)
Digital peripheral signals 1,020 inputs/outputs
Analog peripheral signals 254 inputs/outputs
Configuration possibility via KS2000
Data transfer rates 2/4/8/16 Mbaud, adjustable by means of configuration switch
Bus interface FSMA standard, IEC 872-2
Data transfer medium 1,000 Вµm plastic fiber optic
Power supply 24 V DC (-15%/+20%)
Input current 70 mA + (total K-bus current)/4, 500В mA max.
Starting current 2.5 x continuous current
Recommended fuse ≤ 10 A
Current supply K-bus 1750 mA
Power contacts max. 24 V DC/max. 10 A
Electrical isolation 500 V (power contact/supply voltage/fieldbus)
Distance between stations 40В m plastic fiber optic
Weight approx. 170 g
Operating/storage temperature 0…+55°C/-25…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx
Ex marking ATEX: II 3 G Ex ec IIC T4 Gc
IECEx: Ex ec IIC T4 Gc